5110XM FEATURES

  • Five supervised style B zones
  • One master code
  • Five user codes
  • Seven built-in LED indicators
  • One notification appliance circuit
  • Temporal code compliant
  • Supervised digital dialer
  • Optional panel door mounted silence/reset switch when AHJ approved
  • Supports two-wire compatible smoke detector
  • Supports up to four keypads
  • Backup digital dialer built in
  • Auxiliary form "C" relay
  • Built-in warning buzzer
  • Programmable via 6139R alpha keypad or downloader
  • Supports major communication formats
  • UL864 Listed
  • NFPA 72 compliant
  • MEA Approved
  • Upload/Download capable

APPLICATIONS

The 5110XM Fire Alarm Communicator (DACT - Digital Alarm Communicator Transmitter) is well suited for a variety of applications a stand alone fire control or slave DACT. A diverse line of ADEMCO alarm notification appliances as well as initiating devices supports this powerful control panel. Some of the applications supported are monitoring of sprinkler supervisory or waterflow switches in factory or warehouse environments, fast food chains, department stores, retail stores, library and museums as well as professional and office buildings. This panel complies with the new, June 1,1998 NFPA requirement to alternate testing of dual phone lines on a rotating basis.

INSTALLATION

The 5110XM Fire Alarm Communicator (DACT) has been designed to mount both quickly and easily. It meets all applicable requirements for UL Commercial Fire installations. Remotely program and troubleshoot this panel via ADEMCO's WindowsT based Compass Downloader.

 

SPECIFICATIONS

(Return to top)

Electrical:

Primary power

  • 20VAC, 60Hz, 600mA max
  • Secondary rated 18VAC, 40VA

Quiescent panel current draw:

  • 155mA

Backup battery:

  • 1 2VDC, 7AH min to 14AH max
  • Lead acid battery (gel type)

Charging voltage:

  • 1 3.7VDC, nominal

Alarm power:

  • 12VDC, 1.0A max for notification (bell) output

Aux. standby power:

  • 12VDC,350mA max

Total power:

  • 1.0A from all sources

Aux. relay output:

  • Type: Form C

Standby time:

  • 24 hours with 1A standby load or 60 hours with 210mA max standby load using 14AH battery

Fusing:

  • Battery input, aux. and notification (bell) appliance circuits are protected using PTC circuit protectors. All outputs are power limited

Dialers:

Line seize:

  • Double Pole

Ringer equiv.:

  • 0.7B

Formats:

  • ADEMCO Low Speed, ADEMCO 4+2 press, ADEMCO High Speed, ADEMCO Contact ID, Sescoa and Radionics

Mechanical:

  • Cabinet dimensions -14.5"H X 1 2.5"W X 3"D

Environmental:

  • -10°C to 70°C

Operating temp:

  • 0°C to 50°C

Humidity:

  • 85% RH

EMI:

  • Meets or exceeds the following requirements:
    -FCC Part 15, Class B Device
    -FCC Part 68
    -IEC EMC Directive

AGENCY LISTINGS

The 5110XM has been listed and approved for use in commercial fire applications. It has been listed under the following agency approvals:

Fire

  • UL864/NFPA72 Central and Remote Station DACT and Local, Central Station and Remote Station Control
  • Factory Mutual
  • California State Fire Marshall
  • MEA

COMPATIBLE DEVICES

See ADEMCO Group control accessories compatibility chart for complete list.