5110XM
FEATURES
- Five
supervised style B zones
- One master
code
- Five user
codes
- Seven
built-in LED indicators
- One notification
appliance circuit
- Temporal
code compliant
- Supervised
digital dialer
- Optional
panel door mounted silence/reset switch when AHJ approved
- Supports
two-wire compatible smoke detector
- Supports
up to four keypads
- Backup
digital dialer built in
- Auxiliary
form "C" relay
- Built-in
warning buzzer
- Programmable
via 6139R alpha keypad or downloader
- Supports
major communication formats
- UL864
Listed
- NFPA 72
compliant
- MEA Approved
- Upload/Download
capable
APPLICATIONS
The
5110XM Fire Alarm Communicator (DACT - Digital Alarm Communicator Transmitter)
is well suited for a variety of applications a stand alone fire control
or slave DACT. A diverse line of ADEMCO alarm notification appliances
as well as initiating devices supports this powerful control panel. Some
of the applications supported are monitoring of sprinkler supervisory
or waterflow switches in factory or warehouse environments, fast food
chains, department stores, retail stores, library and museums as well
as professional and office buildings. This panel complies with the new,
June 1,1998 NFPA requirement to alternate testing of dual phone lines
on a rotating basis.
INSTALLATION
The
5110XM Fire Alarm Communicator (DACT) has been designed to mount both
quickly and easily. It meets all applicable requirements for UL Commercial
Fire installations. Remotely program and troubleshoot this panel via ADEMCO's
WindowsT based Compass Downloader.
SPECIFICATIONS
(Return
to top)
Electrical:
Primary
power
- 20VAC,
60Hz, 600mA max
- Secondary
rated 18VAC, 40VA
Quiescent
panel current draw:
Backup
battery:
- 1 2VDC,
7AH min to 14AH max
- Lead acid
battery (gel type)
Charging
voltage:
Alarm
power:
- 12VDC,
1.0A max for notification (bell) output
Aux.
standby power:
Total
power:
Aux.
relay output:
Standby
time:
- 24 hours
with 1A standby load or 60 hours with 210mA max standby load using 14AH
battery
Fusing:
- Battery
input, aux. and notification (bell) appliance circuits are protected
using PTC circuit protectors. All outputs are power limited
Dialers:
Line
seize:
Ringer
equiv.:
Formats:
- ADEMCO
Low Speed, ADEMCO 4+2 press, ADEMCO High Speed, ADEMCO Contact ID, Sescoa
and Radionics
Mechanical:
- Cabinet
dimensions -14.5"H X 1 2.5"W X 3"D
Environmental:
Operating
temp:
Humidity:
EMI:
- Meets
or exceeds the following requirements:
-FCC Part 15, Class B Device
-FCC Part 68
-IEC EMC Directive
AGENCY
LISTINGS
The
5110XM has been listed and approved for use in commercial fire applications.
It has been listed under the following agency approvals:
Fire
- UL864/NFPA72
Central and Remote Station DACT and Local, Central Station and Remote
Station Control
- Factory
Mutual
- California
State Fire Marshall
- MEA
COMPATIBLE
DEVICES
See
ADEMCO Group control accessories compatibility chart for complete list. |